Policy for Fire Life Safety Sequence in High Rise Buildings

LOS ANGELES FIRE DEPARTMENT

Offical seal for the Los Angeles Fire Department

FIRE PREVENTION BUREAU

 

POLICY FOR SEQUENCE OF OPERATIONS


Policy: Attached are the guidelines for the Sequence of Operations for Life Safety Systems in High-Rise Buildings. This basic design guideline may vary depending on building requirements. LADBS has been instructed that all systems must be verified by LAFD prior to approval and/or installation.


Procedure for Sequence of Operations:


1.0 Basic Guidelines for Sequence of Operations for Life Safety Systems in HighRise Buildings


1.1 Follow the guidelines specific to the requirements for the High-Rise Building in question.


1.2 For any additional questions, contact Unit Commanders. 

 

BASIC GUIDELINES FOR SEQUENCE OF OPERATIONS FOR LIFE SAFETY SYSTEMS IN HIGH-RISE BUILDINGS
The following is a basic design guideline.  Systems may vary depending on building requirements.  All systems should be verified by LAFD prior to approval and/or installation.

 Manual PullElevator Lobby
Smoke Detector
Area Smoke/Heat DetectorsDuct Smoke DetectorsElevator Shaft
Smoke/Heat Detector
Sprinkler Water
Flow Switch
Sprinkler Valve
Tamper Switch
Special Extingushing SystemsPre-ActionBuilding Power Failure
Annunciate At Fire Control
Room (Trouble and Alarm)
YesYesYesYesYesYesYesYesYesYes

Annunciate At 24HR Atteded
Remote Location (Trouble and Alarm)

YesYesYesYesYesYesYesYesYesYes
Activate Audible and Visual
Alarm Signals On Floor Of Alarm
YesYesYesYesYesYesNoYesYesNo
Shut Down All Air Handling
On Floor Of Alarm (HVAC)
YesYesYesYesNoYesNoYesYesNo
Close All Smoke/Fire
Dampers On Floor Of Alarm
YesYesYesYesNoYesNoYesYesYes
Release All Motorized and
Electro-Magnetically Held
Doors On Floor Of Alarm
YesYesYesYesNoYesNoYesYesYes
Activate Smoke Evacuation
System On Floor Of Alarm
YesYesYesYesNoYesNoYesYesNo
Recall All Elevators
Serving Floor Of Alarm
NoYesNoNoYesNoNoNoNoYes
Release All Stair Shaft
Door Locks in Building
YesYesYesYesYesYesNoYesYesYes
Activate All Stair Shaft
Pressurization In Building
YesYesYesYesYesYesNoYesYesNo
Open Elevator Shaft
Smoke/Exhaust Dampers
NoNoNoNoYesNoNoNoNoNo
Release Approved
Security Door Locks
YesYesYesYesYesYesNoYesYesYes

If 24 HR on site monitoring is not provided, an approved automatic dialer system shall be installed and report to a LA City approved 24 HR monitoring company                                                                                                                                                               

Full Voice-Evac with page by floor capabilities shall be provided for all new high-rise systems.
                                                     